Building Overview
Modern data centre facility situated in the East of Brussels
Operational since February 2000
Technical space arranged over one floor
Total size (technical space): 5,842 m²
Available fully fitted space: 1,300 m²
Maximum site power: 4 MVA
Carrier connectivity: Level 3, Colt, Codenet, MCI, Belgacom, BNIX, Telenet, BT Ignite, Telia, Traff-X, Scarlet/NetNet, B-Telecom, Eurofiber, Versatel
Modern data centre facility situated in the East of Brussels
Operational since February 2000
Technical space arranged over one floor
Total size (technical space): 5,842 m²
Available fully fitted space: 1,300 m²
Maximum site power: 4 MVA
Carrier connectivity: Level 3, Colt, Codenet, MCI, Belgacom, BNIX, Telenet, BT Ignite, Telia, Traff-X, Scarlet/NetNet, B-Telecom, Eurofiber, Versatel
Technical Summary
Main Power
Three x 1MVA (four ultimate) HV dedicated underground cable feeds to three x 1MVA, (four x 1MVA ultimate) transformer substation
Main Power
Three x 1MVA (four ultimate) HV dedicated underground cable feeds to three x 1MVA, (four x 1MVA ultimate) transformer substation
Generators
Two x 2MVA diesel-driven emergency power generators giving 4 MVA
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24 hour continuous operation at 100% load
24×7 agreement with local fuel supplier
Two x 2MVA diesel-driven emergency power generators giving 4 MVA
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24 hour continuous operation at 100% load
24×7 agreement with local fuel supplier
UPS
Two (three ultimate) x 500kVA Hybrid Rotary UPS modules providing 500kVA (1,000kVA ultimate) total output with N+1 redundancy
15-minute battery autonomy per UPS module
Underfloor power track distribution system
Two (three ultimate) x 500kVA Hybrid Rotary UPS modules providing 500kVA (1,000kVA ultimate) total output with N+1 redundancy
15-minute battery autonomy per UPS module
Underfloor power track distribution system
DC
48VDC power system. 600A “A” + 600A “B” expandable to 2400A “A” + 2400A “B”
Dual-redundant “A” and “B” systems with dual redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
48VDC power system. 600A “A” + 600A “B” expandable to 2400A “A” + 2400A “B”
Dual-redundant “A” and “B” systems with dual redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
Environment
750W/m² average cooling capability over the gross space
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
750W/m² average cooling capability over the gross space
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
Physical
Minimum floor-to-ceiling height: 3,530mm from top of raised floor
800mm raised floor height
Raised Floor loading 10kN/m²
Structural Floor Slab: > 10kN/m²
Minimum floor-to-ceiling height: 3,530mm from top of raised floor
800mm raised floor height
Raised Floor loading 10kN/m²
Structural Floor Slab: > 10kN/m²