Building Overview
Modern datacenter facility situated in the Southeast of Düsseldorf
Operational since November 2000
Technical space arranged over three floors
Total size (technical space): 6,863 m²
Available fully fitted space: 1,866 m²
Available “Shell and Core” space: 1,484 m²
Maximum site power: 6 MVA
Carrier connectivity: Level 3, COLT, DTag, ISIS, Wingas, Versatel
Modern datacenter facility situated in the Southeast of Düsseldorf
Operational since November 2000
Technical space arranged over three floors
Total size (technical space): 6,863 m²
Available fully fitted space: 1,866 m²
Available “Shell and Core” space: 1,484 m²
Maximum site power: 6 MVA
Carrier connectivity: Level 3, COLT, DTag, ISIS, Wingas, Versatel
Technical Summary
Main Power
4 MVA (6 ultimate) supply via dedicated underground 10kV cable feeds to dedicated 2×2MVA (3×2MVA ultimate) 10kV/400V transformer substation
Main Power
4 MVA (6 ultimate) supply via dedicated underground 10kV cable feeds to dedicated 2×2MVA (3×2MVA ultimate) 10kV/400V transformer substation
Generators
One (two ultimate) x 2.5MVA diesel driven emergency power generators giving 2.5 MVA (5MVA ultimate)
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24-hour continuous operation at 100% load
24×7 agreement with local fuel supplier
One (two ultimate) x 2.5MVA diesel driven emergency power generators giving 2.5 MVA (5MVA ultimate)
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24-hour continuous operation at 100% load
24×7 agreement with local fuel supplier
UPS
2×500 kVA (additional 4×625 kVA possible) Hybrid Rotary UPS modules providing 500 kVA total output with N+1 redundancy
15-minute battery autonomy per UPS module
Dual redundant A and B distribution strategy
Underfloor power track distribution system
2×500 kVA (additional 4×625 kVA possible) Hybrid Rotary UPS modules providing 500 kVA total output with N+1 redundancy
15-minute battery autonomy per UPS module
Dual redundant A and B distribution strategy
Underfloor power track distribution system
DC
48VDC power system. 400A “A” + 400A “B” expandable to 2385A “A” + 2385A “B”
Dual-redundant “A” and “B” systems with dual redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
48VDC power system. 400A “A” + 400A “B” expandable to 2385A “A” + 2385A “B”
Dual-redundant “A” and “B” systems with dual redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
Environment
750W/m² average cooling capability over the gross space
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
Physical
Minimum floor-to-ceiling height: 3,700mm from top of raised floor
650mm raised floor height
Raised Floor loading 12kN/m²
Structural Floor Slab:
Ground Floor — 25kN/m² First/Second Floors — 10kN/m²
Minimum floor-to-ceiling height: 3,700mm from top of raised floor
650mm raised floor height
Raised Floor loading 12kN/m²
Structural Floor Slab:
Ground Floor — 25kN/m² First/Second Floors — 10kN/m²