Hamburg datacenter colocation

Süderstrasse 198, 20537 Hamburg, Germany

Building Overview
Modern datacenter facility situated in the Hammerbrook district east of Hamburg
Operational since October 2000
Technical space arranged over two floors
Total size (technical space): 8,394 m²
Available fully fitted space: 1,319 m²
Available “Shell and Core” space: 1,892 m²
Maximum site power: 8 MVA
Carrier Connectivity: Level 3, Colt, DTag, Hansenet
 
Technical Summary
Main Power
8MVA supply via dedicated underground 10kV mains feeds to 3×2MVA, (4×2 MVA ultimate) 10kV/400V transformer station.
 
Generators
Two (four ultimate) x 2MVA diesel-driven emergency power generators giving 4 MVA (8 MVA ultimate)
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24-hour continuous operation at 100% load
24×7 agreement with local fuel supplier.
 
UPS
Two x (three ultimate) x 625kVA Hybrid Rotary UPS modules providing 625kVA (1,250kVA ultimately) total output with N+1 redundancy
15-minute battery autonomy per UPS module
Dual-redundant A and B distribution strategy
Underfloor power track distribution system
 
DC
48VDC power system. 400A “A” + 400A “B” expandable to 2385A “A” + 2385A “B”
Dual-redundant “A” and “B” systems with dual-redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
 
Environment
750W/m² average cooling capability over the gross space
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
 
Physical
Minimum floor-to-ceiling height: 3,700mm from top of raised floor
800mm raised floor height
Raised Floor loading12kN/m²
Structural Floor Slab: Ground Floor — 20kN/m² First Floor — 10kN/m²
 
 
 
Fire Strategy
Use of non-inflammable and low-smoke zero halogen materials where possible
No storage (especially of flammable materials) within technical space
Building split into sealed, independent, fire compartments
Very Intelligent Early Warning (V.I.E.W.) detection
Smoke extract system activated by fire alarm
Double-interlocked pre-action dry pipe sprinkler system
 
Security
Remote 24×7 security monitoring
Full electronic access control system, based on proximity cards with photo and PIN keypads
Biometric Palm-scanners for Colocation areas
Locks on colocation suites and cabinets
Intruder detection system on escape and riser doors
 
Closed Circuit Television (CCTV)
CCTV monitoring and recording of all access points and circulation areas.
 
Building Monitoring System (BMS) 
Local Operations and Control Centre
Network monitoring system with critical alarm repeating to Regional Management Centre
24×7 local monitoring and logging of temperature and humidity conditions and alarms
Critical alarm repeating to Regional Management Centre
Full perimeter underfloor leak detection linked to building monitoring system
 
Telecom Infrastructure
Facility designed to accommodate standard rack/cabinets of 2,200mm nominal height
Power is normally distributed underfloor, fibre and copper cabling distributed overhead (fibre within a managed containment system, copper within a heavy duty racking system)
Fibre entry to the building via two independent points
 
General Facilities
Dedicated loading area — delivery hours 8.00–18.00 (Mon to Fri)
Customer test room (27 m²) and storage area (203 m²)
Goods lift — 1.4m wide x 2.6m high (maximum load 1,500kg)