Building Overview
Modern datacenter facility situated on the eastern edge of Munich
Operational since October 2000
Technical space arranged over two floors
Total size (technical space): 6,114 m²
Available fully fitted space: 2,454 m²
Maximum site power: 6 MVA
Modern datacenter facility situated on the eastern edge of Munich
Operational since October 2000
Technical space arranged over two floors
Total size (technical space): 6,114 m²
Available fully fitted space: 2,454 m²
Maximum site power: 6 MVA
Technical Summary
Main Power
6MVA supply via underground 10kV ringmain to dedicated 3×2MVA 10kV/400V transformer substation
Main Power
6MVA supply via underground 10kV ringmain to dedicated 3×2MVA 10kV/400V transformer substation
Generators
One (three ultimate) x 2MVA diesel-driven emergency power generators giving 2 MVA (6MVA ultimate)
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24-hour continuous operation at 100% load
24×7 agreement with local fuel supplier
One (three ultimate) x 2MVA diesel-driven emergency power generators giving 2 MVA (6MVA ultimate)
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24-hour continuous operation at 100% load
24×7 agreement with local fuel supplier
UPS
Two (four ultimate) x 625kVA Hybrid Rotary UPS modules providing 625kVA (1,875kVA ultimate) total output with N+1 redundancy
15-minute battery autonomy per UPS module
Dual-redundant A and B distribution strategy
Underfloor power track distribution system
Two (four ultimate) x 625kVA Hybrid Rotary UPS modules providing 625kVA (1,875kVA ultimate) total output with N+1 redundancy
15-minute battery autonomy per UPS module
Dual-redundant A and B distribution strategy
Underfloor power track distribution system
DC
48VDC power system. 400A “A” + 400A “B” expandable to 2385A “A” + 2385A “B”
Dual-redundant “A” and “B” systems with dual-redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
48VDC power system. 400A “A” + 400A “B” expandable to 2385A “A” + 2385A “B”
Dual-redundant “A” and “B” systems with dual-redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
Environment
750W/m² average cooling capability over the gross space
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
750W/m² average cooling capability over the gross space
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
Physical
Minimum floor-to-ceiling height: 3,555mm from top of raised floor
650mm raised floor height
Raised floor loading 12kN/m²
Structural Floor Slab: Ground floor — 25kN/m² First floor — 10kN/m
Minimum floor-to-ceiling height: 3,555mm from top of raised floor
650mm raised floor height
Raised floor loading 12kN/m²
Structural Floor Slab: Ground floor — 25kN/m² First floor — 10kN/m