Building Overview
Modern datacenter facility in the Nanterre district of Paris, to the West of the City Centre
Operational since June 1999
Technical space arranged over one floor
Total size (technical space): 4,245 m²
Available fully fitted space: 1,475 m²
Maximum site power: 8 MVA
Modern datacenter facility in the Nanterre district of Paris, to the West of the City Centre
Operational since June 1999
Technical space arranged over one floor
Total size (technical space): 4,245 m²
Available fully fitted space: 1,475 m²
Maximum site power: 8 MVA
Technical Summary
Main Power
8MVA supply via dedicated quad-redundant underground 20kV cable feeds to dedicated redundant 4MVA 20kV/400V transformer substations
Main Power
8MVA supply via dedicated quad-redundant underground 20kV cable feeds to dedicated redundant 4MVA 20kV/400V transformer substations
Generators
Two x 1.2MVA diesel-driven emergency power generators giving 2.4 MVA
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24-hour continuous operation at 100% load
24×7 agreement with local fuel supplier
Two x 1.2MVA diesel-driven emergency power generators giving 2.4 MVA
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24-hour continuous operation at 100% load
24×7 agreement with local fuel supplier
UPS
Three x 420kVA Hybrid Rotary UPS modules providing 840kVA total output with N+1 redundancy
15 minute battery autonomy per UPS module
Underfloor power track distribution system
Three x 420kVA Hybrid Rotary UPS modules providing 840kVA total output with N+1 redundancy
15 minute battery autonomy per UPS module
Underfloor power track distribution system
DC
48VDC power system (4500A expandable to 6000A)
Single bus system with dual-redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
48VDC power system (4500A expandable to 6000A)
Single bus system with dual-redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
Environment
750W/m² average cooling capability over the gross space
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
Physical
Minimum floor-to-ceiling height: 4,117mm from top of raised floor
750mm raised floor height
Raised floor loading 12kN/m²
Structural floor slab 2.5kN/m²
Minimum floor-to-ceiling height: 4,117mm from top of raised floor
750mm raised floor height
Raised floor loading 12kN/m²
Structural floor slab 2.5kN/m²