Frankfurt
datacenter colocation
Rüsselsheimer Strasse 22, 60489 Frankfurt am Main, Germany
Building Overview
Modern datacenter facility situated close to Mainzer Landstrasse in the West of Frankfurt
Operational since June 1999
Technical space arranged over 1 floor
Total size (technical space): 4,333 m²
Available fully fitted space: 1,144 m²
Maximum site power: 4 MVA
Carrier connectivity: Level 3, Colt, DTag, WorldCom
Modern datacenter facility situated close to Mainzer Landstrasse in the West of Frankfurt
Operational since June 1999
Technical space arranged over 1 floor
Total size (technical space): 4,333 m²
Available fully fitted space: 1,144 m²
Maximum site power: 4 MVA
Carrier connectivity: Level 3, Colt, DTag, WorldCom
Technical Summary
Main Power
4MVA supply via dedicated dual redundant underground 10kV cable feeds to dedicated 2×2MVA 10kV/400V transformer substation
Main Power
4MVA supply via dedicated dual redundant underground 10kV cable feeds to dedicated 2×2MVA 10kV/400V transformer substation
Generators
One (two ultimate) x 2MVA diesel driven emergency power generators giving 2 MVA (4MVA ultimate)
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24 hour continuous operation at 100% load
24×7 agreement with local fuel supplier
One (two ultimate) x 2MVA diesel driven emergency power generators giving 2 MVA (4MVA ultimate)
Automatic start in less than one minute to feed 100% of the facility
Generators tested monthly
Fuel storage (Diesel) for 24 hour continuous operation at 100% load
24×7 agreement with local fuel supplier
UPS
Two (three ultimate) x 625kVA Hybrid Rotary UPS modules providing 625kVA (1,250kVA ultimate) total output with N+1 redundancy
15-minute battery autonomy per UPS module
Dual redundant A and B distribution strategy
Underfloor power track distribution system
Two (three ultimate) x 625kVA Hybrid Rotary UPS modules providing 625kVA (1,250kVA ultimate) total output with N+1 redundancy
15-minute battery autonomy per UPS module
Dual redundant A and B distribution strategy
Underfloor power track distribution system
DC
48VDC power system. 4860A expandable to 6500A
Single bus system with dual redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
48VDC power system. 4860A expandable to 6500A
Single bus system with dual redundant “A” and “B” distribution
Four hours of battery autonomy
Underfloor direct A and B feeds from PDU to fuse panel
Environment
750W/m² average cooling capability over the gross space
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
750W/m² average cooling capability over the gross space
Temperature regulated overall to 21°C+/- 2°C
Humidity regulated overall to 50%RH +/- 10%
Technical areas positively pressurized to minimize dust ingress
Physical
Minimum floor to ceiling height: 2,980mm from top of raised floor
750mm raised floor height
Raised Floor loading 14kN/m²
Structural Floor Slab: 10kN/m²
Minimum floor to ceiling height: 2,980mm from top of raised floor
750mm raised floor height
Raised Floor loading 14kN/m²
Structural Floor Slab: 10kN/m²
Fire Strategy
Use of non-inflammable and low smoke zero halogen materials where possible
No storage (especially of flammable materials) within technical space
Building split into sealed, independent, fire compartments
Very Intelligent Early Warning (V.I.E.W.) detection above and below raised floor
Smoke extract system activated by fire alarm
Double-interlocked pre-action dry pipe sprinkler system
No storage (especially of flammable materials) within technical space
Building split into sealed, independent, fire compartments
Very Intelligent Early Warning (V.I.E.W.) detection above and below raised floor
Smoke extract system activated by fire alarm
Double-interlocked pre-action dry pipe sprinkler system
Security
Remote 24×7 security monitoring
Full electronic access control system, based on proximity cards with photo and PIN keypads
Biometric Palm-scanners in addition for Colocation areas
Locks on colocation suites and cabinets
Intruder detection system on all doors and windows
Remote 24×7 security monitoring
Full electronic access control system, based on proximity cards with photo and PIN keypads
Biometric Palm-scanners in addition for Colocation areas
Locks on colocation suites and cabinets
Intruder detection system on all doors and windows
Closed Circuit Television (CCTV)
CCTV monitoring and recording of all access points and circulation areas
CCTV monitoring and recording of all access points and circulation areas
Building Monitoring Systems (BMS)
Local Operations and Control Centre
Network monitoring system with critical alarm repeating to Regional Management Centre
24×7 local monitoring and logging of temperature and humidity conditions and alarms
Full perimeter underfloor leak detection linked to building monitoring system
Local Operations and Control Centre
Network monitoring system with critical alarm repeating to Regional Management Centre
24×7 local monitoring and logging of temperature and humidity conditions and alarms
Full perimeter underfloor leak detection linked to building monitoring system
Telecom Infrastructure
Facility is designed to accommodate standard rack/cabinets of 2,200mm nominal height
Power is normally distributed underfloor, fibre and copper cabling distributed overhead (fibre within a managed containment system, copper within a heavy-duty ladder rack system)
Fibre entry to the building is via four independent points
Facility is designed to accommodate standard rack/cabinets of 2,200mm nominal height
Power is normally distributed underfloor, fibre and copper cabling distributed overhead (fibre within a managed containment system, copper within a heavy-duty ladder rack system)
Fibre entry to the building is via four independent points
General Facilities
Dedicated loading area — delivery hours 08.00-18.00 (Mon to Fri)
Dedicated loading area — delivery hours 08.00-18.00 (Mon to Fri)